Superheated Steam Table — 160 bar (16 MPa)

Specific volume, internal energy, enthalpy, entropy, density and isobaric specific heat of superheated steam at 160 bar (16 MPa), computed from IAPWS-IF97 — the same formulation the SimuPipe solver uses. Rows run from the saturation temperature (347.36 °C) to 800 °C in 20 °C steps.

Superheated steam properties at 160 bar (16 MPa) from IAPWS-IF97
T (°C)v (m³/kg)ρ (kg/m³)u (kJ/kg)h (kJ/kg)s (kJ/kg·K)cp (kJ/kg·K)
347.36Sat.9.3081e-3107.43302431.92580.85.246315.2072
3600.01106090.41682538.72715.65.46168.1928
3800.01287877.65132642.22848.35.66805.5538
4000.01428170.02302719.02947.55.81774.4882
4200.01547864.60662783.23030.95.93993.9032
4400.01654960.42802840.23105.06.04533.5333
4600.01753257.03862892.53173.06.13933.2809
4800.01845254.19482941.53236.76.22513.1004
5000.01932451.74982988.13297.36.30452.9671
5200.02015849.60903033.13355.66.37902.8664
5400.02096147.70743076.73412.16.44942.7891
5600.02174045.99903119.43467.36.51642.7290
5800.02249744.44993161.43521.46.58052.6817
6000.02323743.03433202.83574.66.64222.6444
6200.02396241.73233243.83627.26.70182.6149
6400.02467440.52813284.53679.26.75942.5915
6600.02537539.40913324.93730.96.81532.5731
6800.02606638.36483365.23782.26.86972.5587
7000.02674737.38673405.33833.36.92282.5477
7200.02742236.46763445.43884.16.97452.5395
7400.02808935.60143485.43934.97.02512.5337
7600.02875034.78293525.53985.57.07462.5300
7800.02940534.00773565.64036.17.12312.5281
8000.03005533.27193605.74086.67.17062.5277
Reading this table

u is not tabulated independently. Specific internal energy follows from the enthalpy and specific volume as u = h − p·v, with p in MPa and v in m³/kg (1 MPa·m³/kg = 1000 kJ/kg). At 160 bar (16 MPa) that pressure term is worth 480.9 kJ/kg at 800 °C, so u and h are far apart at high pressure and nearly equal at low pressure — a common source of error when the wrong column is read.

The first row is saturated vapour, at 347.36 °C. Below that temperature at 160 bar (16 MPa) the water is a liquid or a two-phase mixture, and this table does not apply — use the saturated tables instead.

Values are IAPWS-IF97, not interpolated. Every row is evaluated directly from the industrial formulation at that exact temperature, so there is no interpolation error between rows. If you need a temperature between the 20 °C steps, the calculator computes it exactly.

Superheated tables at other pressures